Built-in Isolator Type Primary-Secondary Fusion Pole-Mounted CB

The Built-in Isolator Type Primary-Secondary Fusion Pole-Mounted Circuit Breaker  features a one-piece epoxy casting that integrates the disconnector and the main circuit of the circuit breaker. Compared with conventional external disconnectors, the fully sealed design of the isolating blade reduces exposed live points on the primary side, facilitates operation and maintenance, and eliminates the risk of phase-to-phase short circuits caused by exposed isolating blades.

Specifications

Specifications Product Image
Power frequency withstand voltage (1min) (rms), phase-to-phase and phase-to-ground / open contact: 42 / 48kV
Auxiliary power voltage: DC/AC 24V
Rated short-circuit making current (peak): 50kA
Secondary circuit 1min power frequency withstand voltage: 2kV
Partial discharge of complete unit (at 14.4kV): ≤5pC
Mechanical life (circuit breaker / disconnector): ≥10,000 / 3,000 operations
Rated peak withstand current: 50kA
Rated voltage: 12kV
Rated current: 630A
Rated short-circuit breaking current (rms): 20kA
Rated short-circuit current breaking operations: ≥30 times
Rated short-time withstand current (4s): 20kA
Rated frequency: 50Hz
Isolating gap: ≥120mm
Lightning impulse withstand voltage (peak), phase-to-phase and phase-to-ground / open contact: 75 / 85kV
Individual auxiliary power consumption: 4W / 8W

Features

Three-position indication for isolating function: isolation observation window, isolating position indicator, and isolating live indicator, ensuring visible isolating gap while enhancing safety
Voltage sensor uses CVT principle with secondary electrical isolation; secondary open contact withstand voltage meets 2kV/1min
Pole body integrates phase voltage/current sensors, zero-sequence voltage/current sensors, load-side voltage sensor, and power take-off source; can be flexibly configured per user requirements, eliminating on-site wiring and facil
Avoids issues such as magnetic saturation of electromagnetic transformers and voltage resonance; measurement range is significantly wider and easier to guarantee
Use of sensors eliminates the problems of electromagnetic CT secondary open circuit and PT secondary short circuit; secondary output is low-voltage signal, offering higher safety and reliability
Isolating switch features built-in fully sealed and fully insulated design, excellent weather resistance, maintenance-free, and long service life
Isolating switch adopts direct-drive transmission structure with few mechanical transmission parts, ensuring reliable operation
Main circuit of isolating switch and circuit breaker uses annular one-piece casting molding with outer silicone rubber composite insulation, offering reliable performance and excellent weather resistance